Plan Review Notes
Plan Review Notes For Permit 00101300
Permit Number 00101300
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASESUBMIT AIC RATINGS FOR
 MAIN DISCONNECT AND PANEL. ALL MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110-9. AND 215-5
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS. PER
 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE SEE RISER DIAGRAM. YOU
 SHOW 1/0 CONDUCTORS FOR A 200A SERVICE.
 PLEASE SEE 310-15 AND 310-16 OF NEC.
  
 4)NOTE: PLEASE HAVE BLDG STEEL AS PART
 OF THE GROUNDING ELECTRODE CONDUCTOR
 PER 250-50. PLEASE SHOW.
  
 5)NOTE:PLEASE NOTE THAT OUTLET FOR
 GARAGE ARE TO BE GFI/GFI PROTECTED PER
 210-8. PLEASE SHOW.
  
 6)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 PER 210-8-A-6.PLEASE SHOW
  
 7)NOTE: PLEASE INCLUDE MAIN DISCONNECT
 ON PLAN. NOT SHOWN WITH METER.
  
 8)NOTE: MISSING WP GFI FOR A/C UNITS
 ON SIDE OF HOUSE.
  
 9)NOTE:PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) ON PANEL SCHEDULE PER
 210-11-C-3. #12 AND 20A
  
 10)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING ALONG WALL SPACE 2`6`12` RULE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 659-8096 EXT 8372