| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASESUBMIT AIC RATINGS FOR |
| | MAIN DISCONNECT AND PANEL. ALL MUST BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110-9. AND 215-5 |
| | |
| | 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS. PER |
| | NFPA-72 2-2.1.1.1 |
| | |
| | 3)NOTE: PLEASE SEE RISER DIAGRAM. YOU |
| | SHOW 1/0 CONDUCTORS FOR A 200A SERVICE. |
| | PLEASE SEE 310-15 AND 310-16 OF NEC. |
| | |
| | 4)NOTE: PLEASE HAVE BLDG STEEL AS PART |
| | OF THE GROUNDING ELECTRODE CONDUCTOR |
| | PER 250-50. PLEASE SHOW. |
| | |
| | 5)NOTE:PLEASE NOTE THAT OUTLET FOR |
| | GARAGE ARE TO BE GFI/GFI PROTECTED PER |
| | 210-8. PLEASE SHOW. |
| | |
| | 6)NOTE: ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED |
| | PER 210-8-A-6.PLEASE SHOW |
| | |
| | 7)NOTE: PLEASE INCLUDE MAIN DISCONNECT |
| | ON PLAN. NOT SHOWN WITH METER. |
| | |
| | 8)NOTE: MISSING WP GFI FOR A/C UNITS |
| | ON SIDE OF HOUSE. |
| | |
| | 9)NOTE:PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) ON PANEL SCHEDULE PER |
| | 210-11-C-3. #12 AND 20A |
| | |
| | 10)NOTE: PLEASE SEE 210-52 FOR OUTLET |
| | SPACING ALONG WALL SPACE 2`6`12` RULE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL |
| | |
| | DEWEY PALMER |
| | ELECTRCIAL PLAN REVIEW |
| | 659-8096 EXT 8372 |