2001-01-08 00:00:001) FIRE ALARM CONTROL PANEL IN TAMAYO
 IS TO BE CONNECTED TO C BASE BUILDING
 FIRE ALARM SYSTEM.
 2) FIRE ALARM SYSTEM IS TO BE AUDIBLE
 THROUGHOUT TENANT SPACE WHEN ACTIVATED.
 3) DUCT SMOKE DETECTORS WHEN ACTIVATED
 ARE TO SHUT DOWN AIR HANDLING DEVICES
 AND ACTIVATE FIRE ALARM SYSTEM.
 4) FIRE ALARM SYSTEM IS TO BE TESTED
 AFTER INSTALLATION WITH FIRE RESCUE
 PERSONNEL.