| Plan Review Notes For Permit 00101295 |
| Permit Number |
00101295 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE ALARM CONTROL PANEL IN TAMAYO | | | IS TO BE CONNECTED TO C BASE BUILDING | | | FIRE ALARM SYSTEM. | | | 2) FIRE ALARM SYSTEM IS TO BE AUDIBLE | | | THROUGHOUT TENANT SPACE WHEN ACTIVATED. | | | 3) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | ARE TO SHUT DOWN AIR HANDLING DEVICES | | | AND ACTIVATE FIRE ALARM SYSTEM. | | | 4) FIRE ALARM SYSTEM IS TO BE TESTED | | | AFTER INSTALLATION WITH FIRE RESCUE | | | PERSONNEL. |
|