Plan Review Notes
Plan Review Notes For Permit 00101258
Permit Number 00101258
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SHT.ID-1-THE PLUMBING CODE IN EFFECT
 IS THE 1994 EDITION OF THE STANDARD
 PLUMBING CODE.COUNTYWIDE AMENDMENT TO
 SPC SEC.101.
  
 2)SUBMIT OCCUPANT LOAD BASED ON
 HABITABLE SQ.FOOT AREA PER SPC SEC.
 407.1.3.NU
  
 3)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO A HEIGHT OF 4' PER
 SBC SEC.1204.2.
  
 4)SUBMIT FIRE SAFING DETAIL AND UL
 ASSEMBLY # FOR PIPE PENETRATIONS THRU
 RATED WALLS.REFER TO 1996 EDITION OF
 UL FIRE RESISTIVE DIRECTORY.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.4.,SBC CH.35
  
 5)SHT.P-1-HEATER PAN REQS.MIN.OF 1"
 DRAIN PER SPC SEC.507.8.2.
  
 6)HEATER PAN SHALL COMPLY W/SPC SEC.
 507.8.2.
  
 7)VACUUM RELIEF VALVE SHALL COMPLY W/SPC
 SEC.507.1.2.,ANSI Z21.22.
  
 8)SHT.P-5-VENT FOR SHOWER & F.D.SHALL BE
 BETWWEN THE FIXTURE DRAINS.SPC 901.2.
  
 PLAN REVIEW DOES NOT INCLUDE MEDICAL
 GAS.
  
 CALL IF YOU HAVE ANY QUESTIONS.
 561-8096 EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.