| Plan Review Notes For Permit 00101258 |
| Permit Number |
00101258 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.ID-1-THE PLUMBING CODE IN EFFECT | | | IS THE 1994 EDITION OF THE STANDARD | | | PLUMBING CODE.COUNTYWIDE AMENDMENT TO | | | SPC SEC.101. | | | | | | 2)SUBMIT OCCUPANT LOAD BASED ON | | | HABITABLE SQ.FOOT AREA PER SPC SEC. | | | 407.1.3.NU | | | | | | 3)FLOORS AND WALLS IN TOILET ROOMS SHALL | | | BE NONABSORBENT TO A HEIGHT OF 4' PER | | | SBC SEC.1204.2. | | | | | | 4)SUBMIT FIRE SAFING DETAIL AND UL | | | ASSEMBLY # FOR PIPE PENETRATIONS THRU | | | RATED WALLS.REFER TO 1996 EDITION OF | | | UL FIRE RESISTIVE DIRECTORY.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.4.,SBC CH.35 | | | | | | 5)SHT.P-1-HEATER PAN REQS.MIN.OF 1" | | | DRAIN PER SPC SEC.507.8.2. | | | | | | 6)HEATER PAN SHALL COMPLY W/SPC SEC. | | | 507.8.2. | | | | | | 7)VACUUM RELIEF VALVE SHALL COMPLY W/SPC | | | SEC.507.1.2.,ANSI Z21.22. | | | | | | 8)SHT.P-5-VENT FOR SHOWER & F.D.SHALL BE | | | BETWWEN THE FIXTURE DRAINS.SPC 901.2. | | | | | | PLAN REVIEW DOES NOT INCLUDE MEDICAL | | | GAS. | | | | | | CALL IF YOU HAVE ANY QUESTIONS. | | | 561-8096 EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|