| Plan Review Notes For Permit 00101258 |
| Permit Number |
00101258 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | ON PLAN. SHOULD READ NFPA 101 LIFE | | | SAFETY CODE 1985 EDITION INSTEAD OF | | | 1994 EDITION. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR SPACE. | | | 3) PLEASE PROVIDE MORE DETAILS ON | | | EMERGENCY GENERATOR AND FUEL STORAGE | | | AREA ON GENERATOR. | | | 4) PLANS DO NOT INDICATE IF THE EXISTING | | | BUILDING IS FIRE SPRINKLER PROTECTED. | | | 5) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR NEW FIRE ALARM EQUIPMENT PLANNED | | | FOR BUILDING. | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR MEDICAL GAS SYSTEMS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 | | | ON 10-30-00 CALLED LEWIS AND ASSOCIATES | | | AND REQUESTED MORE INFORMATION. |
|