| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** |
| | |
| | 1)NOTE: AS ASKED FOR AND REQ`D FROM |
| | FIRST REVIEW. PLEASE SUBMIT AIC RATING |
| | FOR MAIN AND PANELS. PER 110-9/215-5 |
| | |
| | 2)NOTE: PLEASE NOTE ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE ARE TO BE GFI/GFI |
| | PROTECTED PER 210-8-A-6 PLEASE SHOW |
| | |
| | 3)NOTE: PLEASE SEE MISSING SD LOWER |
| | LEVEL. |
| | |
| | 4)NOTE: PLEASE NOTE THAT THE PLANS ARE |
| | NOW SHOWING COMPLETE REWIRE? IF CATV |
| | AND TELEPHONES ARE GOING TO BE INSTALLED |
| | THEN THEY MUST BE ON PLAN??? |
| | |
| | 5)NOTE: PLEASE NOTE THAT NO PANEL SCHED- |
| | -ULE WAS SUBMITTED AND MISSING BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. AS ASKED FOR |
| | ON PREVIOUS REVIEW. |
| | |
| | 6)NOTE: PLEASE SEE LOAD CALCULATIONS? |
| | YOU SHOW TWO SEPARATE A/C UNITS? PLEASE |
| | SHOW THESE ON PLANS AND SHOW DISCONNECTS |
| | PER 440-11 AND GFI PER MECH CODE 309.1 |
| | PLEASE SHOW IN HOUSE AHU`S. |
| | AS ON PREVIOUS NOTE IF THERE ARE EXIST- |
| | -ING ELECTRICAL CONDITIONS?? PLEASE SHOW |
| | AND PROVIDE CLARIFICATION. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |