| 2001-01-08 00:00:00 | 1)SUBMIT APPLICABLE SIZING TABLE FOR | | | CSST.THE TABLE YOU SUBMITTED IS FOR | | | IRON PIPE.SGC 305.4. | | | | | | 2)INDICATE TYPE OF PIPE CONNECTED TO | | | METER AND PENETRATING FLOOR.IS IT ALL | | | CSST? | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|