2001-07-08 00:00:00BUILDING PLAN REVIEW
 921 ORTEGA RD
 J L HAWKINS
 P: 966-6383
  
 SBC= REFRENCES TO STANDARD BUILDING CODE
 1997 EDITION
  
 1)- SBC 1606.4.1/1707.4.1 AMEND. REQUIES
 PRODUCT TESTING FOR COMPONENTS & CLAD-
 DING MISSING ARE THE PRODUCT APPROVAL
 REPORTS FOR THE NEW FRONT ENTRY DOORS.
  
 1B)- STORM SHUTTERS : THERE IS NO FASTEN
 ING SCHEDULE NOR IS THERE AND INSTALLA-T
 ION KEY FOR WINDOW TO SHUTTER LOCATION.
  
 1C)- DISCREPANCY: THE WINDOW PRODUCT APP
 ROVAL REPORT IS FOR CASEMENT WINDOWS BUT
 THE PLANS INDICATE SINGLE HUNG OR AWNING
 TYPE WINDOW IN ELEVATION VIEW? SLEEPING
 ROOMS REQUIRE EMERGENCY ESCAPE & RESCUE
 OPENINGS MINIMUM SIZES SBC 1005.4.
  
 ROOF FRAMING PLAN : MANSARD ROOF- NOTE-
 SBC TABLE 2308.1"D"NOTE 4 ALLOWS 5/8"
 DIRECT APPLICATION ONTO 2X4 STUDS, THE
 PLYWOOD IF GROOVED, GROOVES NO WIDER
 THAN 1 1/2" & SPACED NO CLOSER THAN 12"
 O.C. WHAT WILL BE USED FOR BACKING FOR
 THE FLASHING SINCE THERE IS NO SUB-
 SUBSHEATHING AND THE FINISH SIDING CAN'T
 GO TO THE ROOF DECK AS INDICATED ON THE
 NEW DETAIL? NEW ROOF PLAN SECTION A DOES
 NOT GIVE ANY STRAPPING INFO?
  
 3)- PROVIDE NOTICE OF COMMENCEMENT
 RECORDED AT THE CLEAK OF THE COUNTY
 COURT OFFICE BEEFORE THE PERMIT CAN BE
 ISSUED.
  
 PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412