| Plan Review Notes For Permit 00101112 |
| Permit Number |
00101112 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE:PLEASE SUBMIT A CLEAR RISER DIA- | | | -GRAM SHOWING WORK BEING DONE. | | | | | | 2)NOTE: YOU SHOW AN EXISTING 200A METER | | | PACK AND YOU ARE INCREASING SERVICE BUT | | | NOT METERBANK?? PLEASE SHOW EXISTING | | | RISER CONDUCTORS FOR SERVICE INCREASE. | | | | | | 3)NOTE: PLEASE SEE WHERE IT IS PROPOSED | | | TO INCREASE PANEL TO 200A WITH #1 WIRE. | | | THIS IS NOT PERMITTED PER NEC. | | | | | | 4)NOTE: PLEASE DIVIDE LOAD CALCULATIONS | | | FOR EACH PANEL AND ONE FOR TOTAL SERVICE | | | PLEASE LAYOUT/SHOW PER NEC AND ART215-5. | | | THE TOTAL SQ FT SHOWN IS 2000. IS THIS | | | FOR MAIN HOUSE? GARAGE/APT? OR BOTH? | | | | | | 5)NOTE: PLEASE SHOW ELECTRICAL REWORK | | | IN KITCHEN THAT IS PROPOSED ON APPLICAT- | | | -ION.PLEASE SHOW LAYOUT OF FLOOR PLAN | | | FOR CHANGES. | | | | | | 6)NOTE: PLEASE SEE NEC 310-15. #4 IS NOT | | | RATED FOR 125A SERVICE OR PANEL. | | | | | | PLEASE SUBMIT PLANS WITH MORE DETAIL. | | | PLEASE SEE CITY/COUNTY ADMINISTRATIVE | | | CODE 104.2 AND 104.2.7. | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|