| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO; | | | 1.R/A REQUIRED FROM UPSTAIRS MASTER | | | SUITE ALSO. | | | 2.REVISE AIR FLOW CALKULATIONS FIRST | | | FLOOR 1 1/2 TON UNIT IS NOT CAPABLE | | | OF PUSHING 840 CFM'S OR INSTALL A | | | 2 TON UNIT. | | | 3.REVISED DRAWINGS REQUIRED BEFORE FINAL | | | A/C INSPECTION. |
|