| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) THE PLAN DOES NOT INDICATE IF THE | | | ENTIRE WEST WALL IS ONE HOUR FIRE | | | SEPARATED. | | | 2) THE PLAN DOES NOT INDICATE IF THE | | | ENTIRE EAST WALL IS ONE HOUR FIRE | | | SEPARATED. | | | 3) WHAT TYPE OF OCCUPANCY IS LOCATED | | | NEXT TO THE WEST WALL OF THE TENANT | | | SPACE. | | | 4) NO UL NUMBER PROVIDED FOR THE FIRE | | | RATING. | | | 5) NO DOOR SCHEDULE PROVIDED WITH PLANS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|