| Plan Review Notes For Permit 00101075 |
| Permit Number |
00101075 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) EXITING INTO THE STOCKROOM IS ALLOWED | | | ONLY IF THE FOLLOWING CONDITIONS EXIST: | | | AN AISLE OF AT LEAST 44 INCHES IS | | | PROVIDED AND MAINTAINED, THE DOOR | | | LEADING TO THE STOCKROOM IS NOT SUBJECT | | | TO LOCKING, AND NOT MORE THAN 50 | | | PERCENT OF EXIT ACCESS IS PROVIDED | | | THROUGH STOCKROOM. | | | 2) INTERIOR FINISH TO BE CLASS A OR B. | | | 3) PLEASE CORRECT DEAD-END OF MORE THAN | | | 20 FEET. | | | 4) STORAGE AREA TO BE AT LEAST ONE HOUR | | | FIRE RATED WITH A RATED FIRE DOOR AND | | | CLOSER SEPARATING IT FROM THE DISPLAY | | | AREA SINCE NO FIRE SPRINKLERS ARE | | | PRESUMED TO BE PRESENT. | | | 5) PLEASE INDICATE THE TYPE OF STORAGE | | | PLANNED FOR THE STORAGE AREA. | | | | | | PLANS REVEIWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|