Plan Review Notes
Plan Review Notes For Permit 00101075
Permit Number 00101075
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) EXITING INTO THE STOCKROOM IS ALLOWED
 ONLY IF THE FOLLOWING CONDITIONS EXIST:
 AN AISLE OF AT LEAST 44 INCHES IS
 PROVIDED AND MAINTAINED, THE DOOR
 LEADING TO THE STOCKROOM IS NOT SUBJECT
 TO LOCKING, AND NOT MORE THAN 50
 PERCENT OF EXIT ACCESS IS PROVIDED
 THROUGH STOCKROOM.
 2) INTERIOR FINISH TO BE CLASS A OR B.
 3) PLEASE CORRECT DEAD-END OF MORE THAN
 20 FEET.
 4) STORAGE AREA TO BE AT LEAST ONE HOUR
 FIRE RATED WITH A RATED FIRE DOOR AND
 CLOSER SEPARATING IT FROM THE DISPLAY
 AREA SINCE NO FIRE SPRINKLERS ARE
 PRESUMED TO BE PRESENT.
 5) PLEASE INDICATE THE TYPE OF STORAGE
 PLANNED FOR THE STORAGE AREA.
  
 PLANS REVEIWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910