| Plan Review Notes For Permit 00101066 |
| Permit Number |
00101066 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | WINDOWS ON 2ND AND 3RD FLOORS SHALL BE | | | IMPACT RESISTANT TYPE. | | | FIRST FLOOR GLAZING CAN BE PROTECTED BY | | | STORM SHUTTERS. | | | PROVIDE CURRENT REPORT FOR STORM SHUTTER | | | ALSO IF SHUTTERS ARE USED,INSTALLATION | | | AND STORAGE PLAN SHALL BE SUBMITTED FOR | | | APPROVAL BY THE BUILDING OFFICIAL. | | | SUBMIT RECORDED NOTICE OF COMMENCEMENT. | | | | | | SUBMIT SIGNED AND SEALED CALCULATIONS | | | AT EACH OPENING[NEGATIVE AND POSITIVE | | | PRESSURES]. | | | | | | SUBMIT COPY OF SIGNED CONTRACT TO VERIFY | | | CONSTRUCTION VALUE [$7500]???TOO LOW!! | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096 | | | EXT: 8456 |
|