| Plan Review Notes For Permit 00101025 |
| Permit Number |
00101025 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER FS AND FL. | | | ADMINISTRATIVE CODE. PLANS ARE TO BE | | | SIGNED AND SEALED BY ENGINEER OF RECORD | | | 61G15-25.002 AND 471.025 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | MAIN DISCONNECT AND PANEL. ALL MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9. SHOW PER 215-5 | | | | | | 3)NOTE: PLEASE SEE THAT NO LOAD CALCULAT | | | -IONS WERE SUBMITTED/SHOWN?? 215-5 | | | | | | 4)NOTE: PLEASE SHOW PANEL SCHEDULE PER | | | 215-5 AND PLEASE MAKE SURE TO LIST THE | | | REQ`D DEDICATED BATH(S) CIRCUIT(S) PER | | | 210-11-C-3 AND 210-52D. | | | | | | 5)NOTE; PLEASE SHOW RECEPT FOR JACUZZI | | | W/ GFI PROTECTION NOTED. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|