Plan Review Notes
Plan Review Notes For Permit 00100965
Permit Number 00100965
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/AND
 PANELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT PER 110-9. PER 215-5
  
 2)NOTE: PLEASE SEE PANELS AND RISER
 DIAGRAM. PLEASE CORRELATE THE MLO AND
 MCB SHOWN??
  
 3)NOTE: PLEASE INCLUDE AND SHOW BLDG.
 STEEL AS PART OF THE GROUNDING ELECTRODE
 SYSTEM PER 250-50.
  
 4)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE
 PER 210-11-C-3. AND 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372