| Plan Review Notes For Permit 00100965 |
| Permit Number |
00100965 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS/AND | | | PANELS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT PER 110-9. PER 215-5 | | | | | | 2)NOTE: PLEASE SEE PANELS AND RISER | | | DIAGRAM. PLEASE CORRELATE THE MLO AND | | | MCB SHOWN?? | | | | | | 3)NOTE: PLEASE INCLUDE AND SHOW BLDG. | | | STEEL AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM PER 250-50. | | | | | | 4)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) ON PANEL SCHEDULE | | | PER 210-11-C-3. AND 215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|