| Plan Review Notes For Permit 00100919 |
| Permit Number |
00100919 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-27 00:00:00 | NOTES: | | | | | | 1.NO AIR BALANCE OR OUTSIDE AIR CALCS. | | | ASHRAE 62-89. | | | | | | 2.NO DUCT SMOKE DETECTORS INDICATED. | | | 97 SMC 609.1 & 406.4 & NFPA 90A | | | 4-4.4.3 | | | | | | 3.DO WINDOWS IN BATHROOMS WORK?NO | | | EXHAUST FANS INDICATED IN BATHROOMS. | | | 97 SMC 503.3. |
|