| Plan Review Notes For Permit 00100919 |
| Permit Number |
00100919 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-30 00:00:00 | THE SCOPE OF WORK SHOWN ON THE REVISIONS | | | IS REQUIRED TO BE DRAWN BY AN | | | ARCHITECT.INCLUDE DIMENSIONS AND | | | DETAILS IN ACCORDANCE WITH GOOD | | | ARCHITECTURAL PRACTICE.SHOW OR | | | PROVIDE NEW RATED DOOR S FOR THE STAIR | | | ENCLOSURE, FIRE RATED TENANT SEPARATION | | | WHERE APPLICABLE AND PROVISIONS FOR | | | HANDICAP ACCESSIBILITY. | | | | | | SHOW THE METHOD OF FIRE RATED | | | PENETRATION PROTECTION FOR THE | | | MECHANICAL SERVICES. | | | | | | SHOW THE FIRE SPRINKLER LAYOUT FOR THE | | | CHANGED FLOOR PLAN. | | | THE ORIGINAL PERMIT VALUATION OF | | | $6000.00 IS FAR TOO LOW FOR THIS WORK. | | | THE VALUE EXCEEDS $25,000.00.PLEASE | | | PAY ADDITIONAL OR NEW PERMIT FEES AS | | | NECESSARY. |
|