| Plan Review Notes For Permit 00100905 |
| Permit Number |
00100905 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) HYDRAULIC CALUCLATIONS FOR FIRE | | | SPRINKLER SYSTEM ARE TO BE SUBMITTED AT | | | TIME OF PERMIT APPLICATION. NONE | | | WERE SUBMITTED AND THE PLAN REVIEW | | | COMMENTS INDICATE THAT THEY WILL | | | BE SUBMITTED BY THE FIRE SPRINKLER | | | CONTRACTOR. | | | 2) PLEASE CLEARLY IDENTIFY EMERGENCY | | | LIGHT FIXTURE LOCATIONS WITHIN | | | TENANT SPACE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|