2001-01-08 00:00:00****************PROVISO*****************
 1)MIN.CLEAR FLOOR SPACE UNDER DRINKING
 FOUNTAIN SHALL BE 27" PER FACBC SEC.
 4.15.5.SEE SHT.A5.5.DETAIL #7.
  
 2)SHT.A5.5-DETAIL #1-HEIGHT OF TOILET
 PAPER HOLDER SHALL BE A MIN.OF 19" PER
 FACBC SEC.4.16.6,FIG.29(B).
  
 3)POINT OF USE WATER HEATER SHALL NOT
 INFRINGE ON THE CLEAR FLOOR SPACE REQD.
 FOR THE LAV.OR WATER CLOSET PER FACBC
 SEC.4.16.2.,4.19.2.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.