| Plan Review Notes For Permit 00100905 |
| Permit Number |
00100905 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER DRAWINGS. PLEASE | | | PROVIDE HYDRAULIC CALCULATIONS WITH | | | SPRINKLER DRAWINGS. | | | 2) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON PLANS. CUT SHEETS ON DEVICES | | | PLANNED FOR USE ARE NEEDED. A WIRING | | | DIAGRAM IS NEEDED. A SEPARATE PERMIT | | | IS REQUIRED. | | | 3) CLEARLY INDICATE ALL ILLUMINATED | | | EXIT SIGNS AND EMERGENCY LIGHT FIXTURES | | | LOCATED WITHIN THE TENANT SPACE. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8095,EXT.8497 | | | 835-2910 |
|