Plan Review Notes
Plan Review Notes For Permit 00100905
Permit Number 00100905
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS. PLEASE
 PROVIDE HYDRAULIC CALCULATIONS WITH
 SPRINKLER DRAWINGS.
 2) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. CUT SHEETS ON DEVICES
 PLANNED FOR USE ARE NEEDED. A WIRING
 DIAGRAM IS NEEDED. A SEPARATE PERMIT
 IS REQUIRED.
 3) CLEARLY INDICATE ALL ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHT FIXTURES
 LOCATED WITHIN THE TENANT SPACE.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8095,EXT.8497