2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE COVER SHEET. THE 1996
 NEC IS SHOWN. WE ARE UNDER THE "99" NEC.
 PLEASE SEE NOTES FOR ELECTRICAL PLANS
 ON E0-0. THE 96 TO 99 CHANGES SOME CODES
 REFERENCED.
  
 2)NOTE: PLEASE SEE NOTES ON PANELS SCHED
 -ULES FOR TRACK LIGHTING? THIS IS NOT
 IN THE "99' NEC UNDER THE CODE REF. THE
 CODE ART: IS 220-12B PLEASE MAKE NOTE.
  
 3)NOTE: OUTLET SPACING TO MEET LOCAL
 AMENDMENTS PER 210-50. EVERY 20` OF WALL
 SPACE INCLUDING STORAGE AREAS.IF THERE
 ARE ANY QUESTIONS PLEASE CALL.
  
 4)NOTE: JUST A NOTE.AS PER COLOR CODING
 OF CONDUCTORS ON E4-0. LOCAL AMENDMENTS
 FOR 277/480 BROWN/PURPLE/YELLOW.
 IT IS NOTED THAT NO 277/480 IS BEING IN-
 -STALLED.
  
 PLEASE MAKE THE ABOVE MINOR CHANGES AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  