Plan Review Notes
Plan Review Notes For Permit 00100882
Permit Number 00100882
Review Stop B
Sequence Number 4
Notes
Date Text
2001-02-12 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS DRAWINGS PACKAGE SUBMITTED IS
 THE SAME PACKAGE THAT WAS SUBMITTED
 AND REJECTED ORIGINALLY. NOTHING WAS
 DONE TO REVISE THE PREVIOUS COMMENTS.
 2-REVISE ENGINEERED TRUSS DRAWINGS.
 THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING (NOTE: KEEP IN MIND
 THAT SOME MODELS ARE TWO STORY).
 TABLE 1606.2A SBC 1997.
 3-DESIGN CONSIDERATIONS AT BOTTOM OF
 ENGINEERED TRUSSES STATE "WALL HEIGHT"
 SBC 1997 USES MEAN ROOF HEIGHT, NOT
 "WALL HEIGHT". REVISE AS REQUIRED.
 4-TRUSS ENGINEER TO HAVE ORIGINAL
 SIGNATURE ON TRUSS LAYOUT. CHAPTER 471
 OF FLORIDA STATUTES.
 5-ENGINEERED TRUSS DRAWINGS HAVE TWO
 DIFFERENT SIGNATURES. WHY?. SEE
 CHAPTER 471 OF FLORIDA STATUTES.
 REVISE AS REUIRED.
 6-UPDATE ALL GENERAL TRUSS DETAILS AND
 SIGN, SEAL AND DATE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 BE CAREFUL NOT TO SIGN AND SEAL
 DOCUMENTS THAT ARE PREPARED BY OTHER
 ENGINEER. SEE CHAPTER 471 FL. STATUTES
 7-CLARIFY WHY THERE ARE TWO ENGINEERED
 TRUSSES T12 WITH DIFFERENT LOADS?.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
  
 NOTE:
 THIS CHECKLIST APPLIES TO THE FOLLOWING
 PERMITS: 00100886, 00100888, 00100890
 AND 00100894.