| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE "AO". WILL NEED ELEVATION |
| | CERTIFICATE. |
| | 2-REVISE SURVEYS AS REQ'D. SEE COMMENTS. |
| | 3-CLARIFY SIZE OF EGRESS WINDOWS AT 2ND |
| | FLOOR BEDRMS. DESCRIPTION OF WINDOWS, |
| | WINDOW SIZES CALLED & PRODUCT APPROVAL |
| | DON'T MATCH. REVISE/CLARIFY AS REQ'D. |
| | 4-MODEL C DOESN'T COMPLY WITH TABLE 600 |
| | OF SBC 1997 WHEN USING THE SLIDING |
| | GLASS DOORS OPTION. |
| | 9'-8"+4"=10'-0" UP TO 10' IS 20% OP'NG |
| | 5-SOIL TEST REPORT RECOMMENDS FOOTINGS |
| | TO HAVE 18" EMBEDMENT. REVISE FOOTINGS |
| | AS REQUIRED OR PROVIDE CALCS AND/OR |
| | REASON WHY RECOMMENDATIONS ARE NOT |
| | NECESSARY TO FOLLOW. |
| | 6-SIGNED, SEALED AND DATED SOIL TEST |
| | REPORT WAS NOT INCLUDED IN THIS PACK. |
| | PLEASE SUBMIT. |
| | 7-SPECIFY GLASS AREAS TO HAVE SAFETY |
| | GLASS. EG: KITCHEN WINDOW. |
| | SECTION 2405.2 SBC 1997. |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | -HORIZONTAL SLIDERS (IT'S EXPIRED). |
| | -FIREPLACES UL LISTING AND SPECS. |
| | -TWO HOUR CONCRETE BLOCK CERTIFICATION |
| | FROM MANUFACTURER'S ENGINEER STATING |
| | THAT CONCRETE BLOCK EQUIVALENT |
| | THICKNESS COMPLIES WITH ASTM C140 FOR |
| | 2 HR FIRE RESISTANCE. |
| | SECTION 709.3 SBC 1997. |
| | -WINDOW MULLIONS. |
| | -NOTE: USE ONLY ONE TYPE OF PRODUCT |
| | APPROVAL: SBCCI OR DADE COUNTY TO |
| | AVOID CONFLICTS AND MISMATCH. |
| | 9-REVISE ENERGY CALCULATIONS FOR MODEL D |
| | THERE ARE 4 BEDROOMS, NOT THREE. |
| | 10-STORM PANELS: |
| | -PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS UNDER A SEPARATE PERMIT. |
| | 11-SEE COMMENTS ATTACHED AND ON PLANS, |
| | INCLUDING THOSE BY THE OTHER TRADES. |
| | 12-SPECIFY DRAFSTOPPING AT 2ND FLOOR |
| | FRAMING PLAN. SEC. 2305.2 SBC 1997. |
| | SPECIFY MATERIAL AND LOCATION. |
| | 13-TRUSS DRAWINGS: |
| | -REVISE ENGINEERED TRUSSES: THERE IS |
| | ONLY ONE MEAN ROOF HEIGHT FOR ENTIRE |
| | BUILDING. TABLE 1606.2.A SBC 1997. |
| | -DESIGN CONSIDERATIONS AT BOTTOM OF |
| | ENGINEERED TRUSSES STATE "WALL HEIGHT" |
| | SBC REFERS TO MEAN ROOF HEIGHT, NOT |
| | "WALL HEIGHT". REVISE AS REQUIRED. |
| | -TRUSS ENGINEER TO HAVE ORIGINAL |
| | SIGNATURE ON TRUSS LAYOUT. |
| | CHAPTER 471 FLORIDA STATUTES. |
| | -ENGINEERED TRUSS DRAWINGS HAVE TWO |
| | DIFFERENT SIGNATURES. REVISE AS REQ'D. |
| | BY CHAPTER 471 FLORIDA STATUTES. |
| | -UPDATE AND SIGN, SEAL AND DATE ALL |
| | GENERAL TRUSS DRAWINGS. |
| | NOTE: DON'T USE OLD COPIES WITH THE |
| | SEAL OF ANOTHER ENGINEER. |
| | -CLARIFY WHY THERE ARE TWO DIFFERENT |
| | T12 TRUSSES?. |
| | |
| | |
| | NOTES: |
| | |
| | A)PLEASE USE THE 11"X17" SHEETS FOR |
| | RESUBMITTALS. IT'S EASIER TO HANDLE |
| | AND FILE. |
| | B)IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |
| | C)THIS PROVISO APPLIES TO PERMIT NUMBERS |
| | 00100886, 00100888, 00100890 AND |
| | 00100894. |