Plan Review Notes
Plan Review Notes For Permit 00100882
Permit Number 00100882
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO;
  
 1.PAGE BIR-MP-1 AND B-MP-1. SANITARY
 RISER DIAGRAM; TUB VENT MUST BE WASHED
 BY A FIXTURE.94 SPC SEC. 921.4.2.
 LAUNDRY TUB IS AN OPTION SO VENT FOR
 TUB WILL NOT ALWAYS HAVE A FIXTURE
 TO WASH THE TUB VENT.
  
 2.SAME PAGES AS ABOVE. WATER RISER
 DIAGRAM IS NOT SIZED PROPERLY. TWO
 FIXTURES ON 1/2" COLD AND FOUR
 FIXTURES ON 1/2" HOT. COUNTY WIDE
 AMENDMENTS 607.7.