| Plan Review Notes For Permit 00100882 |
| Permit Number |
00100882 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO; | | | | | | 1.SECONDARY DRAIN PROTECTION REQUIRED | | | FOR ALL A/H INSIDE THE DWELLING UNIT | | | 97 SMC SEC. 304.8.6.2. | | | | | | 2.APT. B-1. A/H NOT CAPABLE OF DELIVERY | | | OF 1200 CFM. PAGE BIR-MP-1 SHOWS 3 | | | TON CONDENSOR UNIT ON FLOOR PLAN BUT | | | AIR CONDITIONING SCHEDULE ON PAGE | | | B-MP-4 SHOWS 2 1/2 TON SYSTEM. | | | | | | 3. MISSING PAGE BMP-4. |
|