2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE CALCULATED AT 125%.
 LIGHTING ETC.
  
 2)NOTE: LOAD THAT IS SHOWN, ALREADY
 EXCEEDS THE 80% PERMITTED OF BRKR RATING
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING PER
 220-12B
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 MAKE CORRECTIONS FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372