| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE CALCULATED AT 125%. | | | LIGHTING ETC. | | | | | | 2)NOTE: LOAD THAT IS SHOWN, ALREADY | | | EXCEEDS THE 80% PERMITTED OF BRKR RATING | | | | | | 3)NOTE: PLEASE SHOW TRACK LIGHTING PER | | | 220-12B | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | | MAKE CORRECTIONS FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|