| 2001-01-08 00:00:00 | ************DENIED********************** | | | | | | 1. 1997 SMC 505.4 REQUIRES MIN. 1" PER | | | FOOT SLOPE BACK TOWARD HOOD OR APPROVED | | | RESIDUE TRAP. TRAP APPEARS TO BE IN | | | ANOTHER SPACE OR OTHERWIZE UNACCESSIBLE | | | FOR CLEANING AND MONITORING. PROVIDE | | | INFORMATION ON APPROVAL OF GREASE TRAP | | | AS INDICATED AND LOCATION IN RELATION TO | | | OTHER BUILDING COMPONENTS. | | | 2. PROVIDE REQUIRED SLOPE ON DUCT. | | | 3. PROVIDE MANUFACTURES INFORMATION | | | SHOWING APPROVED TRANSITION METHOD FROM | | | DUCT WRAP TO ENCLOSURE. | | | 4. NFPA 96 4-3.4.3 REQUIRES WHERE | | | PERSONNELL ENTRY IS NOT POSSIBLE, | | | ADEQUATE ACCESS FOR CLEANING SHALL BE | | | PROVIDED AT EACH FLOOR.PROVIDE DETAIL. | | | 5.NFPA 96 4-7.2.2 REQUIRES ENCLOSURE TO | | | BE NOT LESS THAN 2 HRS. |
|