| 2001-01-08 00:00:00 | 1) MANAUL PULL STATIONS ARE NOT | | | REQUIRED. | | | 2) FIRE ALARM EQUIPMENT INSTALLED IN | | | ANTHROPOLOGIE SHALL BE INTERFACED WITH | | | THE BASE BUILDING FIRE ALARM SYSTEM. | | | 3) FIRE ALARM SYSTEM WHEN ACTIVATED | | | IS TO BE AUDIBLE THROUGHOUT. | | | 4) FIRE ALARM SYSTEM IS TO BE CLASS A, | | | STYLE D OR ADDRESSABLE. | | | 5) PLEASE PROVIDE A HORN STROBE NEAR | | | THE MAIN ENTRY DOOR LOCATION. | | | 6) DUCT DETECTOR REQUIRED IN AIR | | | HANDLING SYSTEMS OVER 2000 CFM. | | | 7) SMOKE DETECTORS ARE TO BE LOCATED | | | NO CLOSER THAN THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | APPROVED PROVISO: | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|