Plan Review Notes
Plan Review Notes For Permit 00100781
Permit Number 00100781
Review Stop E
Sequence Number 2
Notes
Date Text
2001-05-25 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEAS NOTE THAT PLANS ARE
 SHOWING THREE AHU`S AND ONLY TWO COND
 UNITS? PLEASE SHOW/CLARIFY
  
 2)NOTE: PLEASE NOTE THAT, NEED TO SHOW
 SEPARATE PANEL SCHEDULES FOR "A" AND "C"
 BOTH ARE SHOWN ON SAME SCHED. THIS IS
 FROM FIRST PROVISO.
  
 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND
 FROM FIRST MEANS OF DISCONNECT OF PANELS
 B AND C. CONDUIT ARE SHOWN WITH FEEDERS
 BUT NEED CLARIFICATION ON GROUND? IS
 THIS CONDUIT EMT, RIDGID?
  
 4)NOTE: PLEASE NOTE THAT LOAD SHOWN ON
 CIRCUITS FOR LIGHTINGWAY EXCEED THE
 80% LOAD PERMITTED BY THE NEC.
  
 5)NOTE: PLEASE CLARIFY OUTLET SHOWN
 IN/AT WATER CLOSET ON SECOND FLOOR.
  
 6)NOTE: PLEASE CLARIFY LOCATION OF
 SERVICE. ELECTRICAL INSPECTOR MENTIONED
 THE POSSIBILITY OF SERVICE BEING ON THE
 OTHER SIDE OF HOUSE.
 PLEASE SUBMIT THE PLAN/AS-BUILT FOR A-8
 FOR GARAGE.
  
  
 7) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE NOTE THAT THE PROVISO ASKING FOR
 SOME OF THESE ITEMS WAS GIVEN LAST
 NOVEMBER. THE PLANS ARE JUST NOW BEING
 SUBMITTED ONE DAY BEFORE FINAL??
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372