| Plan Review Notes For Permit 00100781 |
| Permit Number |
00100781 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************** PROVISO ************* | | | | | | 1)NOTE: PLEASE SHOW MORE DETAIL FOR | | | PANELS. MCB ECT. | | | | | | 2)NOTE: PLEASE SEE RISER, PLEASE PROVIDE | | | MORE DETAIL ON WIRE SHOWN FEEDING PANEL | | | 'B'.2" COND W/ 3-????`S. ALSO RISER SHOW | | | -S PANEL 'B' FEEDING PANEL 'B'??? | | | PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE COMPLETE TOTAL LOAD FOR | | | SERVICE ON A-9. | | | | | | 4)NOTE: PLEASE SHOW WHAT THE MEANS OF | | | DISCONNECT IS ON CABANA?? | | | | | | 5)NOTE: PLEASE SHOW THIRD PANEL. | | | | | | 6)NOTE: | | | | | | | | | 7)NOTE: PLEASE LABEL ALL PANELS ON PLANS | | | AND FLOOR LAYOUT. | | | | | | | | | 8)NOTE: PLEASE SHOW ALL CATV AND TELE-ON | | | -PHONE OUTLETS ON FLOOR PLANS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMAITON | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS' | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|