2001-01-08 00:00:001)SIZE SUPPLY LINE AT METER.COMPLY W/
 SGC TABLE 305.4(A).
  
 2)RECALCULATE YOUR BTU LOAD.PLANS NOTE
 389,000 BTU'S.I CALCULATE 455.SGC SEC.
 302.
  
 3)SUBMIT LEGIBLE COPIES OF THE
 APPROPRIATE SIZING TABLES.SGC SEC.302.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  