| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS | | | SHOWING COMPLIANCE W/ ASHRAE 62-89 | | | 2. ACCESS TO AIR HANDLER SHALL COMPLY | | | WITH 1997 SMC 304.4ACCESS TO BE AT | | | LEAST AS LARGE AS THE LARGEST PIECE OF | | | EQUIPMENT AND IN NO CASE LESS THAN 22X36 | | | INCHES. A LEVEL WORKING PLATFORM SHALL | | | BE PROVIDED ON THE CONTROL SIDE AND ANY | | | OTHER SIDE REQUIRED FOR SERVICE. | | | 3. PLUMBING PLAN DOES NOT INDICATE THE | | | LOCATION OF THE CONDENSATE DRAIN TERMIN- | | | ATION OR THE LOCATION OF THE OVERFLOW | | | DRAIN LINE TERMINATION POINT. PLEASE | | | SPECIFY FOR CLARITY. NOTE: LOCAL WATER | | | AUTHORITY DOES NOT PERMIT CONDENSATE TO | | | GO TO SANITARY SEWER. CHECK WITH LAND- | | | LORD FOR LOCATION OF BUILDING CONDENSATE | | | RISER AND PROVIDE CONSPICUOUS LOCATION | | | FOR OVERFLOW DRAIN LINE TO TERMINATE. |
|