| Plan Review Notes For Permit 00100684 |
| Permit Number |
00100684 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE 220-12B FOR LOAD | | | CALCULATIONS FOR TRACK LIGHTING. PLEASE | | | SHOW LENGTHS ETC. | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% (LIGHTING) | | | | | | 3)NOTE: AIC RATINGS FOR MAIN AND PANEL | | | IS BEING SHOWN, BUT PLEASE SUBMIT AIC | | | RATINGS FOR ALL EQUIPMENT INCLUDING | | | 3P60A AND 3P100A DISCONNECTS ON THE | | | LINE AND LOAD SIDE OF TRANSFORMERS. | | | 110-9 AND 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|