Plan Review Notes
Plan Review Notes For Permit 00100684
Permit Number 00100684
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SEE 220-12B FOR LOAD
 CALCULATIONS FOR TRACK LIGHTING. PLEASE
 SHOW LENGTHS ETC.
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (LIGHTING)
  
 3)NOTE: AIC RATINGS FOR MAIN AND PANEL
 IS BEING SHOWN, BUT PLEASE SUBMIT AIC
 RATINGS FOR ALL EQUIPMENT INCLUDING
 3P60A AND 3P100A DISCONNECTS ON THE
 LINE AND LOAD SIDE OF TRANSFORMERS.
 110-9 AND 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372