| Plan Review Notes For Permit 00100651 |
| Permit Number |
00100651 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)LOCATION OF PLUMBING FIXTURES ON | | | SANITARY RISER SHALL CORRELATE W/FLOOR | | | PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | 2)SHOW ALL FIXTURES ON PLUMBING RISER. | | | COUNTYWIDE AMENDMENTS 104.2.1. | | | | | | 3)PROVIDE COMPLETE GAS RISER DIAGRAM FOR | | | REVIEW.SEE ATTACHED GAS REQS. | | | | | | 4)DRY VENTS NOT PERMITTED ON SANITARY | | | SYSTEM.SPC SEC.906.2.1.. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|