Plan Review Notes
Plan Review Notes For Permit 00100646
Permit Number 00100646
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT STORM RISER DIAGRAM SHOWING
 SQUARE FOOTAGE DRAINED BY EACH DRAIN.
 COMPLY W/SPC TABLES 1108.1,1108.2.
  
 2)SUBMIT DEATILS AND CALCULATIONS FOR
 OVERFLOW DRAINAGE.COMPLY W/SPC SECS.
 1109.1-1109.3.AND APPENDIX A,
 TABLE A101.2.
  
 3)2ND FLOOR WATER HEATER SHALL BE
 EQUIPPED W/PAN AND PAN DRAIN AND SHALL
 COMPLY W/SPC SEC.5078.8.1.-507.8.4.
  
 4)CLEARLY SHOW DIMENSIONS (LXW)OF ALL
 SHOWERS.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.