| 2001-01-08 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS AND ON |
| | EACH LEVEL OF A MULTI-LEVEL RESIDENCE. |
| | PER NFPA-72 2-2.1.1.1 |
| | |
| | 2)NOTE: PLEASE SEE LIGHT FIXTURE TYPE IN |
| | BEDROOM #2 AND SEE 410-8 OF THE NEC. |
| | |
| | 3)NOTE: PLEASE SEE 210-52 FOR OUTLETS |
| | ALONG KITCHEN WALL SPACE. |
| | |
| | 4)NOTE: PLEASE SEE OUTLET SPACING IN |
| | PENTHOUSE PER 210-52. HANDRAILS ARE |
| | CONSIDERED WALL SPACE PER NEC. |
| | |
| | 5)NOTE: PLEASE SEE PANEL SCHEDULE "A" |
| | IT SHOWS FEEDING PANEL "B1" INSTEAD OF |
| | PANEL A1?? PLEASE CORRECT. |
| | |
| | 6)NOTE: PLEASE NOTE THAT NO CONDUIT AND |
| | CONDUCTOR SIZES ARE SHOWN FROM MAIN |
| | DISCONNECTS TO PANELS "A" AND "B". |
| | PLEASE SHOW. ALSO SHOW CONDUCTORS FROM |
| | METER TO GUTTER ETC. PLEASE INDICATE |
| | GUTTER SIZE PER NEC 374. |
| | |
| | 7)NOTE: PLEASE INCLUDE BLDG. STEEL AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM |
| | REQ`D PER 250-50. |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL EQUIPMENT BEING INSTALLED. MAIN DISC |
| | -ONNECTS/PANELS. ALL MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | PLEASE SUBMIT RATING PER 215-5. |
| | |
| | 9)NOTE: PLEASE LIST THE REQ`D DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210-52/210-11-C-3 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRCIAL PLAN REVIEW. |
| | 561-659-8096 EXT8372 |