Plan Review Notes
Plan Review Notes For Permit 00100646
Permit Number 00100646
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND ON
 EACH LEVEL OF A MULTI-LEVEL RESIDENCE.
 PER NFPA-72 2-2.1.1.1
  
 2)NOTE: PLEASE SEE LIGHT FIXTURE TYPE IN
 BEDROOM #2 AND SEE 410-8 OF THE NEC.
  
 3)NOTE: PLEASE SEE 210-52 FOR OUTLETS
 ALONG KITCHEN WALL SPACE.
  
 4)NOTE: PLEASE SEE OUTLET SPACING IN
 PENTHOUSE PER 210-52. HANDRAILS ARE
 CONSIDERED WALL SPACE PER NEC.
  
 5)NOTE: PLEASE SEE PANEL SCHEDULE "A"
 IT SHOWS FEEDING PANEL "B1" INSTEAD OF
 PANEL A1?? PLEASE CORRECT.
  
 6)NOTE: PLEASE NOTE THAT NO CONDUIT AND
 CONDUCTOR SIZES ARE SHOWN FROM MAIN
 DISCONNECTS TO PANELS "A" AND "B".
 PLEASE SHOW. ALSO SHOW CONDUCTORS FROM
 METER TO GUTTER ETC. PLEASE INDICATE
 GUTTER SIZE PER NEC 374.
  
 7)NOTE: PLEASE INCLUDE BLDG. STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 REQ`D PER 250-50.
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. MAIN DISC
 -ONNECTS/PANELS. ALL MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE SUBMIT RATING PER 215-5.
  
 9)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-52/210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW.
 561-659-8096 EXT8372