| Plan Review Notes For Permit 00100638 |
| Permit Number |
00100638 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL | | | EQUIPMENT BEING INSTALLED. MAINS/PANEL | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER 110-9 AND 215-5. | | | PLEASE SHOW ELECTRICAL DETAIL FOR PANELS | | | ON PANEL SCHEDULES. MLO? VOLTAGE? ETC | | | PLANS SHOW ONE DISCONNECT AND ONE PANEL | | | AND RISER SHOWS TWO OF EACH??? PLEASE | | | SHOW ON PLANS AND/OR CORRELATE RISER W/ | | | PLANS. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|