Plan Review Notes
Plan Review Notes For Permit 00100638
Permit Number 00100638
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 EQUIPMENT BEING INSTALLED. MAINS/PANEL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110-9 AND 215-5.
 PLEASE SHOW ELECTRICAL DETAIL FOR PANELS
 ON PANEL SCHEDULES. MLO? VOLTAGE? ETC
 PLANS SHOW ONE DISCONNECT AND ONE PANEL
 AND RISER SHOWS TWO OF EACH??? PLEASE
 SHOW ON PLANS AND/OR CORRELATE RISER W/
 PLANS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372