| Plan Review Notes For Permit 00100581 |
| Permit Number |
00100581 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-02-11 00:00:00 | | | | *******************DENIED*************** | | | | | | PLAN SHEET M2.2 - MECHANICAL ROOM #205 | | | & 203 FIRE DAMPERS ARE REQUIRED FOR THE | | | O.A. AND EXHAUST LOUVER.1997 SMC | | | 610.1.2.PROVIDE LOCATION & DETAILS ON | | | PLAN AS PER 1997 SMC 610.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|