| 2001-01-08 00:00:00 | PLUMBING REVIEW NOTES; |
| | |
| | 1.A MIN. OF ONE DRINKING FOUNTAIN PER |
| | FLOOR SHALL BE SUPPLIED PER SPC TABLE |
| | 407. PROVISIONS SHALL BE MADE FOR |
| | PEOPLE WHO HAVE TROUBLE BENDING OR |
| | STOOPING PER FACBC SEC 4.1.3.(10). |
| | |
| | 2.SHT. C-2 SHOW SIZE OF SEWER TAP AND |
| | SANITARY SEWER LINE. |
| | |
| | 3.SUBMIT CALCULATIONS FOR SECONDARY |
| | EMERGENCY DRAINAGE. COMPLY WITH SEC. |
| | SPC. 1109.1 - 1109.3 AND APPENDIX "A". |
| | |
| | 4.SUBMIT UL ASSEMBLY NUMBER OF FIRE |
| | SAFING DETAILS FOR PIPE PENETRATIONS |
| | COUNTYWIDE AMENDMENTS TO SPC. SEC. |
| | 104.2.4. |
| | |
| | 5.SHT. M2.2 BACKFLOW PREVENTER DEVICE |
| | ON MAKE UP WATER SHALL BE FOR HIGH |
| | HAZARD. COMPLY WITH SPC TABLE 606 |
| | |
| | 6.I COULD NOT CHECK T. LARGE'S NOTE 17 |
| | [THE LAYOUT OF THE RESTROOM ON SHT. |
| | A-5.2.1 BY FIRE STAIR 300 DOESN'T |
| | CORRELATE W/A 2.3.1 CLARIFY. SHTS. |
| | WERE NOT SUBMITED. |
| | |
| | 7.DRY VENTS ON WATER CLOSETS NOT |
| | PERMITED PER SPC 906.2.1. |
| | |
| | 8.SANITARY ISOMETRIC RISER DIAGRAM PAGE |
| | P3-1 WASTE STACK (92 F.U.) MUST RUN |
| | UNDIMINISHED IN SIZE TO CONNECTION |
| | OF STACK VENT SPC 714.2 |
| | |
| | 9.WOMENS HANDICAP STALL DOOR SHOWN |
| | (A1.3.1) SWINGING OUT (A4.1.5)SWINGING |
| | IN SWING SHOULDBE OUT OF H/C TURNING |
| | CIRCLE. |
| | |