| Plan Review Notes For Permit 00100581 |
| Permit Number |
00100581 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****CONTINUATION OF PLUMBING PLAN | | | REVIEW COMMENTS. | | | | | | 26)TWO WATER CLOSETS ON A HORIZ.SECTION | | | MAY BE VENTED PER COUNTYWIDE AMENDMENTS | | | TO SPC SEC.911.1.3. | | | | | | 27)DRY VENTS ON WATER CLOSETS NOT | | | PERMITTED PER SPC SEC.906.2.1. | | | | | | 28)CLEARLY DESIGNATE THE FLOOR LEVELS ON | | | THE PLUMBING DRAWINGS.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | 29)VACUUM RELIEF VALVE SHALL BE | | | INSTALLED PER SPC SEC.507.1.2. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|