2001-01-08 00:00:001) PLAN REVIEW COMMENTS, ITEM 4 RESPONSE
 INDICATES THAT VERTICAL SHAFTS ARE
 NON ACCESSIBLE. NFPA 13, INDICATES "ONE
 SPRINKLER SHALL BE INSTALLED AT THE TOP
 OF ALL SHAFTS".
 2) COULD NOT LOCATE FPO-1 OR FP3-1.
 AS INDICATED ON THE PLAN REVIEW COMMENTS
 REGARDING THE FIRE PUMP AND STANDPIPE
 SYSTEM.
  