Plan Review Notes
Plan Review Notes For Permit 00100581
Permit Number 00100581
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 THESE ARE NOTES IN RESPONSE TO LETTER
 AND NOTES NOT FULLY ADDRESSED FROM FIRST
 REVIEW.PLEASE SEE THE FOLLOWING.
  
 1)NOTE:(NOTE 1)OK BUT NO MORE THAN 6 OCP
 DEVICES MAY BE INSTALLED. TEN (10 )
 SPACES ARE SHOWN.ALLOWING FUTURE
 INSTALLATION OF MORE THAN SIX MEANS OF
 DISCONNECT
  
  
 2NOTE: NOTE 2 OK
  
 3)NOTE: NOTE 3 OK
  
 4)NOTE: PLEASE SEE 230-6 FOR REQ`MENTS
 OF OUTSIDE THE BLDG. 2" ENCASEMENT OF
 CONCRETE. PLEASE CLARIFY THIS ON E3-1
 PLEASE NOTE THAT S-1 WAS NOT IN THE SET
 THAT I REVIEWED. MAYBE THIS IS WHERE
 THIS DETAIL IS LOCATED. PLEASE CLARIFY
 LOCATION OF DETAIL OF POURED CONCRETE
 ENCASEMENT.
  
 5)NOTE: NOTE 5 OK
  
 6)NOTE: NOTE 6 PLEASE CORRELATE E3-1 AND
 E3-2 EMDP ON E3-2 SHOWN AS MLO? YET ON
 E3-1 EMDP IS SHOWN AS 400A MCB.??
 PLEASE CLARIFY.HOW DOES FUTURE GENERATOR
 PROVIDE THE REQ`D EM POWER NOW.?LIGHTING
 FIRE PUMP, ECT
 NOTE: NOTE 7 OK
 8)NOTE: NOTE 8 YOUR REPSONSE IS THAT
 THERE ARE NO CIRCUITS ENTERING MORETHAN
 120 VOLTS. VOLTAGE AT 120V IS NOT PER-
 -MITTED. POWER FOR MAIN BLDG MAY BE
 SHUT DOWN INCASE OF FIRE AND THERE WILL
 STILL BE 120V COMING IN, ENOUGH TO CAUSE
 INJURY OR DEATH. POWER IN ONE BLDG FROM
 TWO SERVICES??? A MEANS OF DISCONNECT IS
 REQ`D IN ELEC ROOM.
 .
  
 9)NOTE: NOTE 9 OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE CALL FOR APPOINTMENT
 WITH MYSELF AND THE CHIEF ELECTRICAL
 INSPECTOR FOR ANY QUESTIONS THAT MAY
 STILL NEED TO BE ADDRESSED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 NOTE: PLEASE SEE 230-70A AND EXPLAIN HOW
 SERVICE READILY ACCESSIBLE. TO MEET NEC
 PLEASE NOTE THAT SERVICE IS SHOWN ON
 SECOND FLOOR UP STAIRS BEHIND TWO
 LOCKED DOORS.