| Date |
Text |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: |
| | |
| | 1). SBC 1804.2 SOILS REPORT / MINIMUM |
| | SOIL BEARING CAPACITY |
| | 2).SS 553.71 THRESHOLD BUILDING- A COPY |
| | OF THE REQUIRED THRESHOLD INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. |
| | 3). SBC. 104.2 ATTACHMENT OF ALL WINDOW |
| | AND DOOR BUCKS.NOTE: 609.2.1.1 EXCEPTION |
| | ALL BUCKS,HEADERS,BLOCKING ETC; IN PART- |
| | ITIONS TO BE APPROVED FIRE RETARDANT |
| | TREATED WOOD. |
| | 4). SBC 1606.4/1707.4.1 GLAZED OPENINGS |
| | REQUIRE TESTING REPORTS FOR LARGE MISSLE |
| | IMPACT RESISTANT GLAZING FOR OPENINGS |
| | BELOW 30' AND SMALL MISSLE IMPACT TESTIN |
| | ABOVE 30'. |
| | 5). SBC 1707.5 INFORMATION ON THE ROOF |
| | TILE TESTING, A SBCCI REPORT OR DADE |
| | COUNTY PRODUCT APPROVAL REPORT. |
| | |
| | BUILDING PLAN REVIEW: |
| | JIM WITMER |
| | (561) 659-8-96 EX 8412 |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RE-SUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISIONS |
| | AND REMOVE AND OR REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING |
| | THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND, WIL |
| | HELP TO EXPEDITE TO YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |