Plan Review Notes
Plan Review Notes For Permit 00100581
Permit Number 00100581
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD PER TABLE 407 OF
 THE SPC.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 2)A MIN.OF 1 DRINKING FOUNTAIN PER FLOOR
 SHALL BE SUPPLIED PER SPC TABLE 407.
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLEBENDING OR STOOPING PER
 FACBC SEC.4.1.3.(10)(A).
  
 3)THE MIN.NUMBER OF REQD.SANITARY
 FACILITIES SHALL BE DETERMINED BY THE
 OCCUPANT LOAD.SEE COMMENT #1.COMPLY W/
 SPC TABLE 407.ADD'L.FIXTURES ARE REQD.
  
 4)SHT.C-2-CLEARLY SHOW SIZE OF SANITARY
 SEWER LINE.
  
 5)TOILET ROOM #130(CHANGING ROOM)SHALL
 BE FULLY H.C.ACCESSIBLE PER FACBC SEC.
 4.1.3.(11).
  
 6)AN ADDITIONAL H.C.STALL IS REQD.IN THE
 WOMEN'S R.R.PER FACBC SEC.4.22.4.
  
 7)PANTRY SINK AND COUNTER(RM.117)SHALL
 COMPLY W/FACBC SEC.4.24.1-4.24.7.
  
 8)BREAK ROOM SINK AND CABINET SHALL
 COMPLY W/4.24.1.-4.24.7.
  
 9)SUBMIT CALCULATIONS FOR SECONDARY
 (EMERGENCY)DRAINAGE.COMPLY W/SPC SEC.
 1109.1-1109.3 AND APPENDIX "A."
  
 10)SHT.4.1.5-DETAIL #1-DOOR ON H.C.STALL
 CANNOT SWING INTO CLEAR FLOOR SPACE
 REQD.FOR URINAL PER FACBC SEC.4.17.5.
  
 11)SHOW THE REQD.WHEELCHAIR TURNING
 SPACE IN ROOM#130(CHANGING ROOM TOILET
 ROOM)FACBC SEC.4.2.3.
  
 12)SHT.4.1.5.-DETAIL #3-WATER CLOSET
 SHALL BE 18"FROM WALL PER FACBC SEC.
 4.16.2.(SEE NOTE #2 ALSO).
  
 13)HEIGHT OF PAPER TOWEL DISPENSER SHALL
 COMPLY W/FACBC SEC.4.2.5,4.2.6.,4.27.2,
 4.27.3.(SEE SHT.4.1.5.)
  
 14)SHOW CLEAR FLOOR SPACE FOR URINAL.
 COMPLY W/FACBC SEC.4.18.3.
  
 15)SHT.4.1.5.-SHOW THE REQD.WHEELCHAIR
 TURNING SPACE IN RESTROOMS #305,306,403,
 407.COMPLY W/FACBC SEC.4.2.3.
  
 16)A FLOOR DRAIN IS REQD.IN THE CHANGING
 ROOM TOILET PER SPC 409.4.1.1.
  
 17)THE LAYOUT OF THE RESTROOM ON SHT.
 A-5.2.1.BY FIRE STAIR 300 DOESN'T
 CORRELATE W/A-2.3.1.CLARIFY.
  
 18)SUBMIT UL ASSEMBLY NUMBER OFFIRE
 SAFING DETAILS FOR PIPE PENETRATIONS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4
  
 19)SHT.M2.2.-BFP DEVICE ON M/U WATER
 SHALL BE FOR HIGH HAZARD.COMPLY W/SPC
 TABLE 606.
  
 20)SHT.C-2-CLEARLY SHOW LOCATION OF CD
 LINES ON CIVIL DRAWINGS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 21)SHOW POINT OF COMPASS ON PLBG.PLANS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 22)INDICATE SLOPE OF STORM DRAIN
 BRANCHES,LEADERS DRAIN AND SEWER.COMPLY
 W/SPC TABLES 1108.1,1108.2.
  
 23)WATER HEATER ABOVE THE FIRST FLOOR
 SHALL BE INSTALLED IN A PAN W/A DRAIN
 AND COMPLY W/SPC SEC.507.8.1.-507.8.4.
  
 24)SHT.P3.1-SANITARY SYSTEM SHALL COMPLY
 W/SPC SEC.914.1 FOR A CIRCUIT AND LOOP
 SYSTEM.VENTS SHALL COMPLY W/SPC SEC.
 920.3.
  
 25)WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY.FIXTURE
 BRANCHES AND WATER CLOSETS ARE NOT
 PERMITTED ON WET VENTS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.911.1.1.
  
 SEE REVIEW STEP#2 FOR CONTINUATION.