| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT OCCUPANT LOAD PER TABLE 407 OF |
| | THE SPC.SEE SPC SEC.407.1.3.FOR ALLOWED |
| | DEDUCTIBLE AREAS. |
| | |
| | 2)A MIN.OF 1 DRINKING FOUNTAIN PER FLOOR |
| | SHALL BE SUPPLIED PER SPC TABLE 407. |
| | PROVISIONS SHALL BE MADE FOR PEOPLE WHO |
| | HAVE TROUBLEBENDING OR STOOPING PER |
| | FACBC SEC.4.1.3.(10)(A). |
| | |
| | 3)THE MIN.NUMBER OF REQD.SANITARY |
| | FACILITIES SHALL BE DETERMINED BY THE |
| | OCCUPANT LOAD.SEE COMMENT #1.COMPLY W/ |
| | SPC TABLE 407.ADD'L.FIXTURES ARE REQD. |
| | |
| | 4)SHT.C-2-CLEARLY SHOW SIZE OF SANITARY |
| | SEWER LINE. |
| | |
| | 5)TOILET ROOM #130(CHANGING ROOM)SHALL |
| | BE FULLY H.C.ACCESSIBLE PER FACBC SEC. |
| | 4.1.3.(11). |
| | |
| | 6)AN ADDITIONAL H.C.STALL IS REQD.IN THE |
| | WOMEN'S R.R.PER FACBC SEC.4.22.4. |
| | |
| | 7)PANTRY SINK AND COUNTER(RM.117)SHALL |
| | COMPLY W/FACBC SEC.4.24.1-4.24.7. |
| | |
| | 8)BREAK ROOM SINK AND CABINET SHALL |
| | COMPLY W/4.24.1.-4.24.7. |
| | |
| | 9)SUBMIT CALCULATIONS FOR SECONDARY |
| | (EMERGENCY)DRAINAGE.COMPLY W/SPC SEC. |
| | 1109.1-1109.3 AND APPENDIX "A." |
| | |
| | 10)SHT.4.1.5-DETAIL #1-DOOR ON H.C.STALL |
| | CANNOT SWING INTO CLEAR FLOOR SPACE |
| | REQD.FOR URINAL PER FACBC SEC.4.17.5. |
| | |
| | 11)SHOW THE REQD.WHEELCHAIR TURNING |
| | SPACE IN ROOM#130(CHANGING ROOM TOILET |
| | ROOM)FACBC SEC.4.2.3. |
| | |
| | 12)SHT.4.1.5.-DETAIL #3-WATER CLOSET |
| | SHALL BE 18"FROM WALL PER FACBC SEC. |
| | 4.16.2.(SEE NOTE #2 ALSO). |
| | |
| | 13)HEIGHT OF PAPER TOWEL DISPENSER SHALL |
| | COMPLY W/FACBC SEC.4.2.5,4.2.6.,4.27.2, |
| | 4.27.3.(SEE SHT.4.1.5.) |
| | |
| | 14)SHOW CLEAR FLOOR SPACE FOR URINAL. |
| | COMPLY W/FACBC SEC.4.18.3. |
| | |
| | 15)SHT.4.1.5.-SHOW THE REQD.WHEELCHAIR |
| | TURNING SPACE IN RESTROOMS #305,306,403, |
| | 407.COMPLY W/FACBC SEC.4.2.3. |
| | |
| | 16)A FLOOR DRAIN IS REQD.IN THE CHANGING |
| | ROOM TOILET PER SPC 409.4.1.1. |
| | |
| | 17)THE LAYOUT OF THE RESTROOM ON SHT. |
| | A-5.2.1.BY FIRE STAIR 300 DOESN'T |
| | CORRELATE W/A-2.3.1.CLARIFY. |
| | |
| | 18)SUBMIT UL ASSEMBLY NUMBER OFFIRE |
| | SAFING DETAILS FOR PIPE PENETRATIONS. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4 |
| | |
| | 19)SHT.M2.2.-BFP DEVICE ON M/U WATER |
| | SHALL BE FOR HIGH HAZARD.COMPLY W/SPC |
| | TABLE 606. |
| | |
| | 20)SHT.C-2-CLEARLY SHOW LOCATION OF CD |
| | LINES ON CIVIL DRAWINGS.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 21)SHOW POINT OF COMPASS ON PLBG.PLANS. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | 22)INDICATE SLOPE OF STORM DRAIN |
| | BRANCHES,LEADERS DRAIN AND SEWER.COMPLY |
| | W/SPC TABLES 1108.1,1108.2. |
| | |
| | 23)WATER HEATER ABOVE THE FIRST FLOOR |
| | SHALL BE INSTALLED IN A PAN W/A DRAIN |
| | AND COMPLY W/SPC SEC.507.8.1.-507.8.4. |
| | |
| | 24)SHT.P3.1-SANITARY SYSTEM SHALL COMPLY |
| | W/SPC SEC.914.1 FOR A CIRCUIT AND LOOP |
| | SYSTEM.VENTS SHALL COMPLY W/SPC SEC. |
| | 920.3. |
| | |
| | 25)WET VENTS SHALL RECEIVE THE DISCHARGE |
| | FROM FIXTURE DRAINS ONLY.FIXTURE |
| | BRANCHES AND WATER CLOSETS ARE NOT |
| | PERMITTED ON WET VENTS.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.911.1.1. |
| | |
| | SEE REVIEW STEP#2 FOR CONTINUATION. |