Plan Review Notes
Plan Review Notes For Permit 00100581
Permit Number 00100581
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************DENIED********************
  
 1. NO FIRE DAMPERS SHOWN AT RATED CORR-
 IDOR WALLS AT DUCT PENETRATIONS. 1997
 SMC 610.6.1 REQUIRES LOCATION AND INSTA-
 LLATION DETAILS TO BE INDICATED ON PLAN
 BY DESIGNER.(PER 610.1)
 2. MENS RM ON M-2.1 HAS A E1(150 CFM)
 W/ 75CFM DIFFUSER AFTER HEATER AND 75CFM
 PRIOR TO HEATER. IS THIS CORRECT?
 3. CLARIFY AIR DIRECTION ON M-2.1 @ (17)
 EXHAUST AIR LOUVER.
 4. PROVIDE ENLARGED DETAIL OF MECHANICAL
 ROOMS SHOWING COMPLIANCE WITH 1997 SMC
 304.2.1 AND MANUFACTURES COIL PULL
 CLEARANCE REQUIREMENTS
 5. SPECIFY CHILLED WATER PIPING MATERIAL
 6. NOTE: NO COMBUSTIBLE MATERIALS ARE
 TO BE USED IN ANY AREA USED AS A RETURN
 AIR PLENUM. (RE: NOTE ON MECHANICAL
 FLOOR PLANS)