| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | | | | 1. NO FIRE DAMPERS SHOWN AT RATED CORR- | | | IDOR WALLS AT DUCT PENETRATIONS. 1997 | | | SMC 610.6.1 REQUIRES LOCATION AND INSTA- | | | LLATION DETAILS TO BE INDICATED ON PLAN | | | BY DESIGNER.(PER 610.1) | | | 2. MENS RM ON M-2.1 HAS A E1(150 CFM) | | | W/ 75CFM DIFFUSER AFTER HEATER AND 75CFM | | | PRIOR TO HEATER. IS THIS CORRECT? | | | 3. CLARIFY AIR DIRECTION ON M-2.1 @ (17) | | | EXHAUST AIR LOUVER. | | | 4. PROVIDE ENLARGED DETAIL OF MECHANICAL | | | ROOMS SHOWING COMPLIANCE WITH 1997 SMC | | | 304.2.1 AND MANUFACTURES COIL PULL | | | CLEARANCE REQUIREMENTS | | | 5. SPECIFY CHILLED WATER PIPING MATERIAL | | | 6. NOTE: NO COMBUSTIBLE MATERIALS ARE | | | TO BE USED IN ANY AREA USED AS A RETURN | | | AIR PLENUM. (RE: NOTE ON MECHANICAL | | | FLOOR PLANS) |
|