| 2001-01-08 00:00:00 | 1) BUILDING WILL BE REQUIRED TO HAVE |
| | A KNOX-BOX FOR EMERGENCY PURPOSES. AN |
| | APPLICATION FOR THIS BOX CAN BE OBTAINED |
| | FROM WEST PALM BEACH FIRE RESCUE, |
| | STATION #1. |
| | 2) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESS TO |
| | COMPLY WITH CITY CODE REQUIREMENTS. |
| | 3) PROVISIONS ARE TO BE MADE FOR AT |
| | LEAST TWO HANDICAPPED PERSONS. |
| | 4) ENTIRE BUILDING IS TO BE COMPLETELY |
| | FIRE SPRINKLER PROTECTED. THIS INCLUDES |
| | ALL MECHANICAL, ELECTRICAL, AND SERVICE |
| | ROOMS. ALSO ALL VERTICAL SHAFTS ARE |
| | TO BE PROTECTED BY FIRE SPRINKLERS. |
| | NO HYDRAULIC CALCULATIONS WERE PROVIDED |
| | WITH FIRE SPRINKLER DRAWINGS. A SEPARATE |
| | PLAN AND PERMIT IS REQUIRED FOR THE |
| | INSTALLATION OF FIRE SPRINKLER SYSTEM. |
| | 5) CLEARLY INDICATE FIRE HYDRANT |
| | LOCATIONS IN RELATIONSHIP TO NEW |
| | BUILDING. |
| | 6) PLEASE PROVIDE INTERIOR FLAME SPREAD |
| | INFORMATION ON ALL INTERIOR FINISHES. |
| | THIS INCLUDES DRAPERIES, SEATS, ETC. |
| | 7) ANY DOOR IN A REQUIRED MEANS OF |
| | EGRESS SUBJECT TO AN OCCUPANCY OF 100 |
| | OR MORE PERSONS SHALL BE EQUIPPED WITH |
| | APPROVED PANIC HARDWARE. IF THEY ARE |
| | FIRE DOORS, THEN THEY ARE TO BE EQUIPPED |
| | WITH APPROVED PANIC FIRE EXIT HARDWARE. |
| | 8)PLEASE PROVIDE TOTAL OCCUPANT LOADS |
| | FOR ALL FLOORS. |
| | 9) AT LEAST ONE USEABLE STAIR IS TO BE |
| | PROVIDED DURING CONSTRUCTION ACTIVITIES. |
| | 10) FIRE HYDRANTS ARE TO BE PROVIDED |
| | PRIOR TO BEGINNING CONSTRUCTION. |
| | 11) A TEMPORARY STANDPIPE IS TO BE |
| | PROVIDED FOR THE BUILDING WHEN IT |
| | REACHES THREE STORIES AND 50 FEET IN |
| | HEIGHT. |
| | 12) PLEASE INDICATE THE TYPE OF STAGES |
| | OR PLATFORMS PLANNED FOR THE AUDITORIUM |
| | AREAS. |
| | 13) PLEASE PROVIDE COMPLETE FIRE ALARM |
| | SYSTEM SHOP DRAWINGS FOR THE FIRE |
| | ALARM SYSTEM. CUT SHEETS, WIRING DIAGRAM |
| | AND FLOOR PLANS ARE TO BE SUBMITTED. |
| | FIRE ALARM SYSTEM AND SPRINKLER SYSTEM |
| | ARE TO BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED BY THE FIRE |
| | RESCUE DEPARTMENT. |
| | 14) PLEASE PROVIDE MORE DETAILS ON OWNER |
| | SUPPLIED CHORAL SEATED RISERS PLANNED |
| | FOR CHORAL REHEARSAL, 335. |
| | 15) ELEVATORS TO COMPLY WITH ANSI A17.1 |
| | AND 4A-47,UNIFORM RULES AND STANDARDS |
| | FOR ELEVATORS. |
| | 16) DOUBLE DOORS LEADING FROM SOUND LOCK |
| | INTO GALLERY, FIRST FLOOR TO BE 20 |
| | MINUTE FIRE DOORS WITH CLOSERS. |
| | 17) PROVIDE COMPLETE PLANS AND PERMITS |
| | FOR THE INSTALLATION OF THE REQUIRED |
| | STANDPIPE SYSTEM AND FIRE PUMP. |
| | 18) PLATFORM CONSTRUCTION TO COMPLY WITH |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION, SECTION 8-3.2.1.3. IS STORAGE |
| | GOING TO BE PERMITTED UNDERNEATH THE |
| | PLATFORM. |
| | 19) PROVIDE FLAMESPREAD DETAILS FOR |
| | PROJECTION SCREEN. |
| | 20) PLEASE PROVIDE CODE SECTIONS FOR |
| | SEATING LAYOUTS SHOWN ON PLANS. |
| | |
| | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |