2001-01-08 00:00:00FAILED
 COMMENTS
 C-2
 NO LARGE TREES ARE TO BE PLANTED ON TOP
 OF EXIST. 4" WM ALONG ACACIA ROAD
 A 5' MINIMUM DISTANCE FROM A LARGE
 TREE TO EXISTING PUBLIC UTILITIES
 MUST BE MAINTAINED.
 CUT ON PUBLIC WM NOT ALLOWED
 C.O. MUST BE INSTALLED AT ROW LINE
 WHERE SANITARY SEWER WILL BE MADE UNTO
 DIXIE.A FDOT ROW PERMIT MAY APPLY.
 EXISTING CURB AND SIDEWALK THAT MAY BE D
 DAMAGED BY CONSTRUCTION MUST RE REPLACED
 WHERE EXIST DRIVEWAY APPROCHES ARE
 ELIMINATED THE SIDEWALK MUST BE REDONE
 AND RECURBED.
 SPECIFY WITH A NOTE THAT WM IN ROW
 MUST BE CLASS 52 CEMENT LINED DIP
  
 METER MUST BE INSTALLED JUST OUTSIDE OF
 PROPERTY. AND A VALVE SHOULD BE
 ADDED AFTER METER TO SHUT SEPERATE
 FIRE AND DOMESTIC SERVICES INCASE ONE
 GOES DOWN.
 NO POLLUTION CONTROL PLAN
 IT MUST SHOWN SILT FENCE AROUND
 CONSTRCUTION AREAS ALONG WITH BALES
 OF HAY AND IT MUST LIST PERVIOIUS AND
 IMPERVIOUS CALCULATIONS WITH 100% TOTAL
 SITE LISTED IN S.F. AND ACRES.
 NEW STORM CHRGES WILL BE CLACUALTED FROM
 THIS TALLY.
 (SEE STORM REQUIREMENTS)
 AFTER REVISIONS ARE MADE PLEASE
 SUBMITT 2 SETS FOR REVIEW TO PUBLIC
 UTILITIES ENGINEERING SERVICES DIV
 1000 45TH ST. ATTENTION DEAN LAUDERMILK
 561 659 8040
 (MAKE SURE YOU USE LATEST STD DETAILS
 FOR UTILITY THEY MAY BE REQUESTED AT
 [email protected]
 HAVE A GREAT DAY.