| Date |
Text |
| 2001-01-08 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE 230-71A. THERE CAN BE |
| | NO MORE THAN SIX MEANS OF DISCONNECT IN |
| | A SINGLE ENCLOSURE. PLEASE SEE MSB |
| | ENCLOSURE SHOWN. THIS SHOWS 10?? PLEASE |
| | CORRECT. |
| | |
| | 2)NOTE: ALSO PLEASE SEE 230-95 FOR THE |
| | REQ`D GFI PROTECTION OF SERVICE. |
| | |
| | 3)NOTE: PLEASE SEE 230-76 AND 230-79 FOR |
| | MEANS OF DISCONNECT REQ`D. SHUNT TRIPS |
| | ARE NOT A SERVICE RATED MEANS OF DISC- |
| | -CONNECT. |
| | |
| | 4)NOTE: PLEASE ALSO SEE 230-70 FOR THE |
| | LOCATION OF THE MEANS OF DISCONNECTS. |
| | PLEASE ALSO NOTE PER LOCAL AMENDMENTS |
| | NO UNPROTECTED MORE THAN 8`INSIDE A |
| | BLDG. |
| | |
| | 5)NOTE: PLEASE SHOW NOTE PER LOCAL |
| | AMENDMENTS FOR COLOR CODING OF 277/480V |
| | SYSTEMS. |
| | |
| | 6)NOTE: PLEASE SUBMIT CLARIFICATION FOR |
| | SERVICE. YOU SHOW EMERGENCY POWER |
| | FOR EMDP? PLEASE SHOW WHERE THIS POWER |
| | IS COMING FROM?????GENERATOR? NOTE: |
| | MEANS OF DISCONNECT ON BLDG. FOR THIS. |
| | |
| | 7)NOTE: ALSO PLEASE SHOW ALL CONTINUOUS |
| | LOADS AT 125% AND INCLUDE LARGEST MOTOR. |
| | LIGHTING LOADS AT 125%.!! |
| | |
| | 8)NOTE: PLEASE NOTE GROUPING OF MAINS |
| | FOR SERVICE AT BLDG AND SERVICE FOR |
| | CHILLERS. POWERED CONTROL CIRCUITS |
| | ENTERING BLDG FROM THE SERVICE FOR THE |
| | CHILLER NEEDS TO HAVE MEANS OF DISC |
| | GROUPED PER 230-72 AND LABELED FOR |
| | LOCATIONS OF EACH MEANS. |
| | |
| | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL EQUIPMENT BEING INSTALLED. PER 110-9 |
| | AND 215-5.SEE MAIN FOR FIRE PUMP CONTR. |
| | |
| | |
| | PLEASE SUBMIT ALL OF THE ABOVE INFORMAT- |
| | -ION FOR REVIEW. IF THERE ARE ANY QUES- |
| | -TIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561-659-8096 EXT 8372 |