Plan Review Notes
Plan Review Notes For Permit 00100581
Permit Number 00100581
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SEE 230-71A. THERE CAN BE
 NO MORE THAN SIX MEANS OF DISCONNECT IN
 A SINGLE ENCLOSURE. PLEASE SEE MSB
 ENCLOSURE SHOWN. THIS SHOWS 10?? PLEASE
 CORRECT.
  
 2)NOTE: ALSO PLEASE SEE 230-95 FOR THE
 REQ`D GFI PROTECTION OF SERVICE.
  
 3)NOTE: PLEASE SEE 230-76 AND 230-79 FOR
 MEANS OF DISCONNECT REQ`D. SHUNT TRIPS
 ARE NOT A SERVICE RATED MEANS OF DISC-
 -CONNECT.
  
 4)NOTE: PLEASE ALSO SEE 230-70 FOR THE
 LOCATION OF THE MEANS OF DISCONNECTS.
 PLEASE ALSO NOTE PER LOCAL AMENDMENTS
 NO UNPROTECTED MORE THAN 8`INSIDE A
 BLDG.
  
 5)NOTE: PLEASE SHOW NOTE PER LOCAL
 AMENDMENTS FOR COLOR CODING OF 277/480V
 SYSTEMS.
  
 6)NOTE: PLEASE SUBMIT CLARIFICATION FOR
 SERVICE. YOU SHOW EMERGENCY POWER
 FOR EMDP? PLEASE SHOW WHERE THIS POWER
 IS COMING FROM?????GENERATOR? NOTE:
 MEANS OF DISCONNECT ON BLDG. FOR THIS.
  
 7)NOTE: ALSO PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% AND INCLUDE LARGEST MOTOR.
 LIGHTING LOADS AT 125%.!!
  
 8)NOTE: PLEASE NOTE GROUPING OF MAINS
 FOR SERVICE AT BLDG AND SERVICE FOR
 CHILLERS. POWERED CONTROL CIRCUITS
 ENTERING BLDG FROM THE SERVICE FOR THE
 CHILLER NEEDS TO HAVE MEANS OF DISC
 GROUPED PER 230-72 AND LABELED FOR
 LOCATIONS OF EACH MEANS.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. PER 110-9
 AND 215-5.SEE MAIN FOR FIRE PUMP CONTR.
  
  
 PLEASE SUBMIT ALL OF THE ABOVE INFORMAT-
 -ION FOR REVIEW. IF THERE ARE ANY QUES-
 -TIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372