| Plan Review Notes For Permit 00100505 |
| Permit Number |
00100505 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-12-03 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, PANEL SCHEDULES | | | SHOW FEEDERS AS 3/0`S AND RISER SHOWS | | | 4/0`S FOR PANELS "L" AND "A/C". PLEASE | | | VERIFY AND CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-659-8096 EXT 8372 |
|