| Plan Review Notes For Permit 00100505 |
| Permit Number |
00100505 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PROVISO FROM | | | LAST REVIEW WAS NOT ADDRESSED. | | | PLEASE NOTE/CLARIFY 225A OCP SHOWN FOR | | | PANELS "L" AND "AC" AND 3/0`S AS THE | | | CONDUCTORS. PLEASE NOTE THAT PROVISO | | | NEEDED THESE TO BE CHANGED BEFORE | | | NEXT PLAN REVIEW/FINAL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 |
|