Plan Review Notes
Plan Review Notes For Permit 00100495
Permit Number 00100495
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE TITLE BLOCK ON SIDE
 OF PLANS. PLANS NOTE THAT THEY ARE NOT
 VALID WITHOUT SEAL. IS THE PERSON IN
 TITLE BLK AN ARCH/ENGINEER UNDER FLORIDA
 ADMIN. 481.221 OR 481.321 IF SO PLEASE
 PROVIDE SEAL/SIG. PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS PER NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE SHOW A/C COND UNIT AND
 DISCONNECT PER 440-11 AND SHOW GFI REC
 FOR A/C UNIT.
  
 4)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52 WALL BY KITCHEN.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. ALL
 MAINS AND PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9.
  
 6)NOTE: PLEASE NOTE THAT YOU SHOW ONLY
 PANEL SCHEDULES FOR PANEL"A". PLEASE
 SHOW OTHER PANELS SHOWN. PLEASE SHOW
 CONDUCTOR SIZES AND CONDUIT SIZES,
 PLEASE SHOW HOW THEY ARE BEING FED SINCE
 NOTHING IN PANEL "A" INDICATES FEEDING
 OTHER PANELS???
 ALSO PLEASE SEE LOAD CALCUALTIONS AT THE
 TOP OF PANEL"A".NO SQ FOOTAGE IS SHOWN
 FOR GENERAL LIGHTING CALCS.??
 PLEASE SEE PANEL SCHEDULE AT THE
 BOTTOM FOR LIGHTING LOAD ??? IT SHOWS
 LIGHTS AS 7431. PLEASE SHOW SQ FT.
  
 7)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-52D AND 210-11-C-3
 MUST BE #12 AND 20A .
  
 8)NOTE: PLEASE SHOW DISC FOR AHU IN CLOS
 -ET.
  
 9)NOTE: PLEASE LABEL OUTLET IN GARAGE AS
 GFI/GFI PROTECTED PER 210-8.
  
 10)NOTE: PLEASE INDICATE WHICH PANELS
 ARE MCB AND MLO.
  
 11)NOTE: PLEASE SEE 250-50 FOR THE REQ`
 MENTS FOR GROUNDING ELECTRODE CONDUCTOR
 GOING TO BLDG STEEL ALSO. PLEASE SHOW
 BLDG STEEL ON RISER WITH CWP.
  
 12)NOTE: PLEASE SEE PLANS,, THERE ARE NO
 CATV AND TELEPHONE OUTLETS SHOWN??
 IS THERE GOING TO BE CATV OR PHONES
 INSTALLED? IF SO THEN ALL LOCATIONS NEED
 TO BE SHOWN ON PLANS.
  
 13)NOTE: PLEASE SHOW OCTAGONS IN BEDROOM
 -S AS FAN/LIGHTS OR DRAW IN. IF THIS IS
 WHATS BEING INSTALLED.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372