| 2001-01-08 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE TITLE BLOCK ON SIDE |
| | OF PLANS. PLANS NOTE THAT THEY ARE NOT |
| | VALID WITHOUT SEAL. IS THE PERSON IN |
| | TITLE BLK AN ARCH/ENGINEER UNDER FLORIDA |
| | ADMIN. 481.221 OR 481.321 IF SO PLEASE |
| | PROVIDE SEAL/SIG. PLEASE CLARIFY. |
| | |
| | 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| | ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- |
| | -ING ROOMS PER NFPA-72 2-2.1.1.1 |
| | |
| | 3)NOTE: PLEASE SHOW A/C COND UNIT AND |
| | DISCONNECT PER 440-11 AND SHOW GFI REC |
| | FOR A/C UNIT. |
| | |
| | 4)NOTE: PLEASE NOTE MISSING OUTLET PER |
| | 210-52 WALL BY KITCHEN. |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL EQUIPMENT BEING INSTALLED. ALL |
| | MAINS AND PANELS MUST BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 6)NOTE: PLEASE NOTE THAT YOU SHOW ONLY |
| | PANEL SCHEDULES FOR PANEL"A". PLEASE |
| | SHOW OTHER PANELS SHOWN. PLEASE SHOW |
| | CONDUCTOR SIZES AND CONDUIT SIZES, |
| | PLEASE SHOW HOW THEY ARE BEING FED SINCE |
| | NOTHING IN PANEL "A" INDICATES FEEDING |
| | OTHER PANELS??? |
| | ALSO PLEASE SEE LOAD CALCUALTIONS AT THE |
| | TOP OF PANEL"A".NO SQ FOOTAGE IS SHOWN |
| | FOR GENERAL LIGHTING CALCS.?? |
| | PLEASE SEE PANEL SCHEDULE AT THE |
| | BOTTOM FOR LIGHTING LOAD ??? IT SHOWS |
| | LIGHTS AS 7431. PLEASE SHOW SQ FT. |
| | |
| | 7)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-52D AND 210-11-C-3 |
| | MUST BE #12 AND 20A . |
| | |
| | 8)NOTE: PLEASE SHOW DISC FOR AHU IN CLOS |
| | -ET. |
| | |
| | 9)NOTE: PLEASE LABEL OUTLET IN GARAGE AS |
| | GFI/GFI PROTECTED PER 210-8. |
| | |
| | 10)NOTE: PLEASE INDICATE WHICH PANELS |
| | ARE MCB AND MLO. |
| | |
| | 11)NOTE: PLEASE SEE 250-50 FOR THE REQ` |
| | MENTS FOR GROUNDING ELECTRODE CONDUCTOR |
| | GOING TO BLDG STEEL ALSO. PLEASE SHOW |
| | BLDG STEEL ON RISER WITH CWP. |
| | |
| | 12)NOTE: PLEASE SEE PLANS,, THERE ARE NO |
| | CATV AND TELEPHONE OUTLETS SHOWN?? |
| | IS THERE GOING TO BE CATV OR PHONES |
| | INSTALLED? IF SO THEN ALL LOCATIONS NEED |
| | TO BE SHOWN ON PLANS. |
| | |
| | 13)NOTE: PLEASE SHOW OCTAGONS IN BEDROOM |
| | -S AS FAN/LIGHTS OR DRAW IN. IF THIS IS |
| | WHATS BEING INSTALLED. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMAITON |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |